Cabur
2CABCSF120C
POWER SUPPLY N 90-264VAC/100-340VDC OUT 24VDC/5A ITEM NAME G6 SGM
Power supplies
Price, availability, and delivery times will be confirmed in your quote.
| Manufacturer | Cabur |
|---|---|
| Part number | XCSF120DP |
| Series | COOL POWER |
|---|---|
| Type | CSF120DP |
| HS code | 85044083 |
| Input rated voltage | 120–230 Vac |
|---|---|
| Input voltage AC | 90…264 Vac |
| Input voltage DC | 100…345 Vdc (derating Uin 0.65 |
| Internal protection fuse | T 3.15 A |
| External protection on AC line | MT: C-4 A / Fuse: T 4 A |
| Output adjustable range | 45…55 Vdc |
|---|---|
| Continuous current | 2.5 A at 45°C |
| Overload limiting | 8 A for >30 s |
| Short circuit peak current | 7.5 A for 50 ms |
| Ripple @ nominal ratings | 30 mVpp |
| Hold up time | 16 ms (120 Vac) / 81 ms (230 Vac) |
| Status indication | LED "DC OK" / LED "Alarm" |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >43.2 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | already fitted with internal ORing diode |
| Efficiency | 86% (120 Vac) / 90% (230 Vac) |
|---|---|
| Dissipated power | 20 W (120 Vac) / 13 W (230 Vac) |
| Operating temperature range | –20…+60°C (derating -2.4 W >45°C) |
| Safety Standard | EN 62368-1, UL508 |
| EMC Standard | EN 61000-3-2, EN 61000-3-3, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, |
| Overvoltage category / pollution degree | II / 2 |
| Protection degree | IP 20 |
| Connection terminal | 2.5 mm² / 2.5 mm² |
| Housing material | aluminium |
| Dimensions (LxHxD) | 40x115x130 mm |